OMRON S8VS-09024A
Power rating | 90 W |
---|---|
Efficiency | 83% TYP. (at 100 VAC input) 85% TYP. (at 200 VAC input) |
Rated input voltage | 100 to 240 VAC |
Allowable input voltage variable range | 85 to 264 VAC 80 to 370 VDC |
Note at DC input | The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). |
Frequency | 50/60 Hz (47 to 450 Hz) |
Rated input curren | 1.9 A TYP. (at 100 VAC input) 1.2 A TYP. (at 200 VAC input) |
Leakage current | 0.5 mA max. (at 100 VAC input) 1.0 mA max. (at 200 VAC input) |
Inrush current | 14 A TYP. (at 100 VAC input) 28 A TYP. (at 200 VAC input) |
Output voltage | 24 VDC |
Output voltage variable range | -10 to +15% (With V. ADJ) |
Ripple | 150 mV max. (Under the rated I/O conditions.) |
Static input variation influence | 0.5% max. at 85 to 264 VAC input, 100% load |
Static load variation influence | 1.5% max. at rated input, 0 to 100% load |
Ambient temperature variation influence | 0.05 %/℃ max. |
Rated output current | 3.75 A |
Start up time | 660 ms TYP. (at 100 VAC input) 420 ms TYP. (at 200 VAC input) |
Hold time | 28 ms TYP. (at 100 VAC input) 136 ms TYP. (at 200 VAC input) |
Overload protection | 105% to 160% of the rated output current, Inverted L voltage drop, Intermittent operation, Automatic reset |
Overvoltage protection | Operated at 130% min. of the rated output voltage, Shut-off Resetting: Reset the power by turning it back (OFF time: at least 3 min) |
Overheat protection | No |
Output voltage indication | Yes (Resolution: 0.1V / Accuracy: ±2% (percentage of output voltage value) ±1 digit max.) |
Output current indication | Yes (Resolution: 0.1A / Accuracy: ±5% F.S. (percentage of rated output current value) ±1 digit max.) |
Peak-hold current indication | Yes (Resolution: 0.1A / Accuracy: ±5% F.S. (percentage of rated output current value) ±1 digit max. / Minimum detectable signal width: 20 ms) |
Maintenance forecast monitor indication | Yes |
Maintenance forecast monitor output | Yes |
Undervoltage alarm output | Yes (open collector output), 30 VDC max., 50 mA max., Sinking (NPN) |
Power failure alarm output | No |
Parallel operation | No (However, backup operation is possible; external diodes required.) |
Series operation | Yes (Up to 2 Power Supplies with external diode) |
Dielectric strength | Between all inputs and all outputs/alarm outputs: 3 kVAC for 1 min (Detection current: 20 mA) Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA) Between all outputs/alarm outputs and all PE terminals: 1 kVAC for 1 min (Detection current: 20 mA) Between all outputs and all alarm outputs: 500 VAC for 1 min (Detection current: 20 mA) |
Insulation resistance | Between all outputs/alarm outputs and all inputs/PE terminals: 100 MΩ min. (at 500 VDC) |
Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s**2, in each 6 directions 3 times |
Output indicator | Yes (color: green) |
Heat radiation | Natural air-cooling |
Construction | Covered type |
Structure | Terminal blocks |
Terminal type | Screw terminal |
Attachment | Terminal block cover |
Weight (Main) | Approx. 490 g |