OMRON S8VK-G48024

  • Sản Phẩm

OMRON S8VK-G48024

  • Liên hệ
Power rating 480 W
Efficiency 89% TYP. (at 100 VAC input)
92% TYP. (at 200 VAC input)
Rated input voltage 100 to 240 VAC
Allowable input voltage variable range 85 to 264 VAC
90 to 350 VDC
Note at DC input The following safety standards apply to a DC input: UL 60950-1, cUR (CSA C22.2 No. 60950-1), EN 50178, EN 60950-1, and Lloyd’s. For a DC input, safety is ensured by an external fuse. Please select for external fuse 12 A 350 VDC or more.
Frequency 50/60 Hz (47 to 450 Hz)
Rated input curren 5.5 A TYP. (at 100 VAC input)
2.7 A TYP. (at 200 VAC input)
Power factor 0.9 min.
Leakage current 0.5 mA max. (at 100 VAC input)
1.0 mA max. (at 200 VAC input)
Inrush current 16 A TYP. (at 100 VAC input (For cold start at 25 ℃))
32 A TYP. (at 200 VAC input (For cold start at 25 ℃))
Output voltage 24 VDC
Output voltage variable range -10 to +15% (With V. ADJ)
Ripple 290 mV(p-p) max. (at 20 MHz (Typical))
Static input variation influence 0.4% max.
Static load variation influence 0.8% max. at rated output voltage and the rated output current, maximum of the fluctuation of the output voltage when changing input voltage slowly at the reach of the permission input voltage
Ambient temperature variation influence 0.05 %/℃ max.
Rated output current 20 A /24 A (Peak current)
Start up time 500 ms TYP. (at 100 VAC input)
300 ms TYP. (at 200 VAC input)
Hold time 40 ms TYP. (at 100 VAC input)
50 ms TYP. (at 200 VAC input)
Overload protection 121% min. of the rated output current, Automatic reset
Overvoltage protection Operated at 130% min. of the rated output voltage, Shut-off
Resetting: Reset the power by turning it back (OFF time: at least 3 min)
Parallel operation Yes (Up to 2 Power Supplies)
Series operation Yes (Up to 2 Power Supplies with external diode)
Dielectric strength Between all inputs and all outputs: 3 kVAC for 1 min (Cut-off current: 20 mA)
Between all inputs and PE terminals: 2 kVAC for 1 min (Cut-off current: 20 mA)
Between all outputs and PE terminals: 1 kVAC for 1 min (Cut-off current: 20 mA)
Insulation resistance Between all outputs and all inputs/ PE terminals: 100 MΩ min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green, lighting from 80 to 90% or more of rated voltage)
Construction Covered type
Structure Terminal blocks
Terminal type Rod terminals
Weight (Main) Approx. 1500 g